Under / Over voltage sensing relay incorporating 219 series internal components coupled with an electronic module. Pull-in voltage is adjustable from 85 to 135VAC for frequencies ranging from 50 to 400 hertz. Hysteresis is typically set for a 4 volt differential but can be user adjustable from 3 to 14 volts when external connections are available.
Additional contact configurations and coil options are available – please use the RFQ/RFI tab above to submit your request.
Additional contact configurations and coil options are available – please use the RFQ/RFI tab above to submit your request.
                    Unit of Measure
                    
               
        
            
                        Specifications
                            |
                        Contacts
                            |
                        Coil
                            |
                        Dielectric Strength
                            |
                        Temperature
                            |
                        Life Expectancy
                            |
                        Miscellaneous
                
            
            Specifications
| Series | N/A 349 | 
| Contact Arrangement | N/A ABX - (SPST - NO + DPDT) | 
| Standard Features | N/A Plug-in with polycarbonate cover | 
| Coil Voltage | N/A 85-135 VAC | 
Contacts
| Contact Configuration | N/A Up to 4 pole | 
| Contact Material | N/A Silver Alloy Gold Diffused | 
| Contact Rating | N/A 10 A | 
| Contact Rating 120 / 240VAC Resistive | N/A 10 A / 10 A | 
| Contact Rating 28VDC Resistive | N/A 10 A | 
| Minimum Contact Load | N/A 500 mW | 
| Contact Resistance, Initial | N/A 100 milliohms max at 6VDC | 
Coil
| Coils Available | N/A AC | 
| Power Consumption | N/A 5 VA | 
| Input Voltage Absolute Maximum | N/A +60% of nominal | 
| Pickup Voltage Range | N/A 3 to 14 volts over drop out | 
| Dropout Voltage Range | N/A 85 to 135VAC | 
| Transient Protection | N/A YES | 
| Duty | N/A Continuous | 